Cooling with hot water
Warm water in. Hot water out. No chillers.
Jets hold a 600 W GPU 25–35 °C above its water (model), so water can arrive at 45 °C and leave at 60 °C (design). Fans alone can reject that heat, or a building can reuse it.
45→60°C
water in, water out, on Nova 8
DesignUp to 98%
of an earlier sealed server's heat into ~65 °C water (93% average)
Measured · third party0L
water evaporated for cooling: sealed loop, dry coolers
Design
More tokens, less opex
Reusable 60 °C heat
1 · GPU chip, 600 W
72–85 °C
Still boosting
Low end at ~3 L/min per GPU pair; high end at the 15 °C design rise
2 · Jet-impingement cold plate
+25–35 °C
chip above its water Simulated
Measured 16 °C at 445 W, 4.8 L/min; scaled to 600 W and Nova 8 flows
3 · Sealed server loop Design
45 → 60 °C
in → out
Coolant rated 60 °C continuous, 80 °C peak
4 · Heat exchanger
58 °C
to facility water
~2 °C approach
5 · Where the heat goes
- Chiller on hot days
- Dry cooler, fans only, all year
- Heats buildings (≥ 55 °C)
- District heat, hot water (≥ 60 °C, with a top-up)
45 °C
Hot day in Reported
≈36 °C
At 45 °C in, water leaves at 60 °C and reaches the building loop at about 58 °C. No chiller in Madrid: dry coolers reject it all year, or radiators reuse it. GPUs ~72–85 °C, depending on flow.
Air-cooled hall today
- Chip ~90 °C Estimate
- Heatsink and fans
- Room air 18–27 °C Reported
- Air handlers
- Chillers
- Cooling towers, water evaporated
Model from the RTX 4090 single-slot plate fit (chip = inlet + 8.5 + 16.4/√(flow) K at 445 W, see T-1), scaled to 600 W. At ~3 L/min per GPU pair the server's water rises ~6 K and the warmer card of each pair sits ~27 K above the server inlet (72 °C on 45 °C water); the 15 K design rise needs ~1.2 L/min per pair, where the fit gives ~77–85 °C before any die-size credit. The page shows that span as 72–85 °C at 45 °C in. The 5 Oct 2026 run used the internal radiator to room air; coolant temperatures were not logged. Hot-water operation on Nova 8 is a design value. 60 °C out sits at the coolant's continuous rating (80 °C peak; wetted-materials specification); margin to be confirmed in materials qualification, so loop water above 60 °C is shown as past the rating. Water out = in + 15 °C at design flow; heat exchanger approach ~2 °C. Chiller-free when supply water ≥ hot-day air + ~5 °C dry-cooler approach. Hot-day air: approximate ASHRAE 0.4% annual cooling design dry-bulb values, rounded (Dublin ≈23, Frankfurt ≈32, Madrid ≈36, Phoenix ≈44 °C; exceeded for roughly 35 hours a year). Building heat (radiators, 55–70 °C) and district heat or domestic hot water (≥ 60 °C, usually with a heat-pump or boiler top-up) thresholds from the application table in the IMR deck. Air-cooled halls supply 18–27 °C air (ASHRAE recommended envelope, reported); air-cooled GPUs run near ~90 °C (estimate, never measured by Nexalus). Up to 98% / 93% average: measured in RISE's lab on an earlier sealed 1OU (OCP) server, not Nova 8; IEEE THERMINIC 2022. Nova 8 capture in Plug-in mode is a design value (up to 90%). 0 L: sealed configurations consume no water for cooling (closed loop, dry coolers; design).
T-2 · Cooling with hot water