Cooling with hot water

Warm water in. Hot water out. No chillers.

Jets hold a 600 W GPU 25–35 °C above its water (model), so water can arrive at 45 °C and leave at 60 °C (design). Fans alone can reject that heat, or a building can reuse it.

45→60°C
water in, water out, on Nova 8
Design
Up to 98%
of an earlier sealed server's heat into ~65 °C water (93% average)
Measured · third party
0L
water evaporated for cooling: sealed loop, dry coolers
Design
More tokens, less opex Reusable 60 °C heat
1 · GPU chip, 600 W 72–85 °C Still boosting Low end at ~3 L/min per GPU pair; high end at the 15 °C design rise
2 · Jet-impingement cold plate +25–35 °C chip above its water Simulated Measured 16 °C at 445 W, 4.8 L/min; scaled to 600 W and Nova 8 flows
3 · Sealed server loop Design 45 → 60 °C in → out Coolant rated 60 °C continuous, 80 °C peak
4 · Heat exchanger 58 °C to facility water ~2 °C approach
5 · Where the heat goes
  • Chiller on hot days
  • Dry cooler, fans only, all year
  • Heats buildings (≥ 55 °C)
  • District heat, hot water (≥ 60 °C, with a top-up)
45 °C
Hot day in Reported
≈36 °C

At 45 °C in, water leaves at 60 °C and reaches the building loop at about 58 °C. No chiller in Madrid: dry coolers reject it all year, or radiators reuse it. GPUs ~72–85 °C, depending on flow.

Air-cooled hall today
  1. Chip ~90 °C Estimate
  2. Heatsink and fans
  3. Room air 18–27 °C Reported
  4. Air handlers
  5. Chillers
  6. Cooling towers, water evaporated
Model from the RTX 4090 single-slot plate fit (chip = inlet + 8.5 + 16.4/√(flow) K at 445 W, see T-1), scaled to 600 W. At ~3 L/min per GPU pair the server's water rises ~6 K and the warmer card of each pair sits ~27 K above the server inlet (72 °C on 45 °C water); the 15 K design rise needs ~1.2 L/min per pair, where the fit gives ~77–85 °C before any die-size credit. The page shows that span as 72–85 °C at 45 °C in. The 5 Oct 2026 run used the internal radiator to room air; coolant temperatures were not logged. Hot-water operation on Nova 8 is a design value. 60 °C out sits at the coolant's continuous rating (80 °C peak; wetted-materials specification); margin to be confirmed in materials qualification, so loop water above 60 °C is shown as past the rating. Water out = in + 15 °C at design flow; heat exchanger approach ~2 °C. Chiller-free when supply water ≥ hot-day air + ~5 °C dry-cooler approach. Hot-day air: approximate ASHRAE 0.4% annual cooling design dry-bulb values, rounded (Dublin ≈23, Frankfurt ≈32, Madrid ≈36, Phoenix ≈44 °C; exceeded for roughly 35 hours a year). Building heat (radiators, 55–70 °C) and district heat or domestic hot water (≥ 60 °C, usually with a heat-pump or boiler top-up) thresholds from the application table in the IMR deck. Air-cooled halls supply 18–27 °C air (ASHRAE recommended envelope, reported); air-cooled GPUs run near ~90 °C (estimate, never measured by Nexalus). Up to 98% / 93% average: measured in RISE's lab on an earlier sealed 1OU (OCP) server, not Nova 8; IEEE THERMINIC 2022. Nova 8 capture in Plug-in mode is a design value (up to 90%). 0 L: sealed configurations consume no water for cooling (closed loop, dry coolers; design).
T-2 · Cooling with hot water